SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel
U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
ConCore 1000
Posilock

7.5

1000
PASS
350 
800
600
150
ConCore 1250
Posilock

8.5

1250
PASS
400 
1000
800
150


SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel
U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
ConCore 1000
Bolted Stringer

9.0

1000
PASS
350 
800
600
150
ConCore 1250
Bolted Stringer

10.0

1250
PASS
400 
1000
800
150
ConCore 1500
Bolted Stringer
10.5
1500
PASS
450
1250
1000
150
ConCore 2000
Bolted Stringer
11.5
2000
PASS
550
1500
1250
150
ConCore 2500
Bolted Stringer
12.0
2500
PASS
650
1500
2000
150