The Performance Charts below are divided into two sections to help you evaluate the overall performance of the systems. The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.
SYSTEM
PERFORMANCE CRITERIA (Tested on Actual Understructure)
|
Panel |
U/S | SYSTEM
WEIGHT (lbs/ft²) |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT
LOADS (lbs) |
Design
Loads* (lbs) |
Safety
Factors* (min 2.0) |
Uniform
Loads (lbs/ft²) |
10
Passes (lbs) |
10,000
Passes (lbs) |
ConCore 1000 |
Posilock |
7.5 |
1000 |
PASS |
350 |
800 |
600 |
150 |
ConCore 1250 |
Posilock |
8.5 |
1250 |
PASS |
400 |
1000 |
800 |
150 |
SYSTEM
PERFORMANCE CRITERIA (Tested on Actual Understructure)
|
Panel |
U/S | SYSTEM
WEIGHT (lbs/ft²) |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT
LOADS (lbs) |
Design
Loads* (lbs) |
Safety
Factors* (min 2.0) |
Uniform
Loads (lbs/ft²) |
10
Passes (lbs) |
10,000
Passes (lbs) |
ConCore 1000 |
Bolted
Stringer |
9.0 |
1000 |
PASS |
350 |
800 |
600 |
150 |
ConCore 1250 |
Bolted
Stringer |
10.0 |
1250 |
PASS |
400 |
1000 |
800 |
150 |
ConCore 1500 |
Bolted
Stringer |
10.5 |
1500 |
PASS |
450 |
1250 |
1000 |
150 |
ConCore 2000 |
Bolted
Stringer |
11.5 |
2000 |
PASS |
550 |
1500 |
1250 |
150 |
ConCore 2500 |
Bolted
Stringer |
12.0 |
2500 |
PASS |
650 |
1500 |
2000 |
150 |