The Performance Charts below are divided into two sections to help you evaluate the overall performance of the systems. The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.


FF1250 SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel
U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
Solid Panels
Bolted Stringer/
Stringerless/
Cornerlock

6.5

1250
2.0
400
1000
1000
150
Perf Panels
Bolted Stringer/
Stringerless/
Cornerlock
6.25
1250
2.0
400
1000
1000
150
Grates
Bolted Stringer/
Stringerless/
Cornerlock
7.25
1250
2.0
400
1000
1000
150

FF3000 SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel
U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
Solid Panels
Bolted Stringer/
Stringerless/
Cornerlock

7.60

2250
2.0
750 
2000
2000
200
Perf Panels
Bolted Stringer/
Stringerless/
Cornerlock

7.40

2000
2.0
750
1500
2000
100

*For more information on design load download the Design Load Technical Bulletin.  All other tests are conducted under CISCA’s recommended test procedures for access floors.
 
 