SYSTEM
PERFORMANCE CRITERIA (Tested on Actual Understructure)
|
Panel | U/S | SYSTEM
WEIGHT (lbs/ft²) |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT
LOADS (lbs) |
Design
Loads* (lbs) |
Safety Factors* (min 2.0) |
Uniform Loads (lbs/ft²) |
10 Passes (lbs) |
10,000 Passes (lbs) |
All Steel 1000 |
Bolted Stringer |
6.0 |
1000 |
PASS |
350 |
400 |
400 |
150 |
All Steel 1250 |
Bolted Stringer |
7.0 |
1250 |
PASS |
400 |
500 |
500 |
150 |
All Steel 1500 |
Bolted Stringer |
8.5 |
1500 |
PASS |
450 |
600 |
600 |
150 |
*For more information on design load download the Design Load Technical Bulletin. All other tests are conducted under CISCA’s recommended test procedures for access floors.