The
Performance Charts below
are divided into two
sections to help you
evaluate the overall
performance of the systems.
The System Performance Criteria
are the most important to
consider because they represent
the performance in a typical
installation. Panel
Only Criteria such as Concentrated
Load is often used to specify
access floor systems; however,
the test is not representative
of an actual installation
because it is performed with
the panel resting on blocks,
not understructure.
System
Performance Criteria
(Tested on Actual
Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
Concore
1000
Posilock
7.5
1000
PASS
350
800
600
150
1000
Concore
1250
Posilock
8.5
1250
PASS
400
1000
800
150
1250
System
Performance Criteria
(Tested on Actual
Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
Concore
1000
Bolted
Stringer
9.0
1000
PASS
350
800
600
150
1000
Concore
1250
Bolted
Stringer
10.0
1250
PASS
400
1000
800
150
1250
Concore
1500
Bolted
Stringer
10.5
1500
PASS
450
1250
1000
150
1500
Concore
2000
Bolted
Stringer
11.5
2000
PASS
550
1500
1250
150
2000
Concore
2500
Bolted
Stringer
12.0
2500
PASS
650
1500
2000
150
2500
*Design
loads and safety factors
are defined in the Technical
Resources/Technical Bulletins
area of the website under "Design Loads".
All other tests are conducted
under CISCA's Recommended Test
Procedures for Access Floors.