The
Performance Charts below
are divided into two sections
to help you evaluate the
overall performance of the
systems. The System
Performance Criteria are
the most important to consider
because they represent the
performance in a typical
installation.
Panel Only Criteria
such as Concentrated Load
is often used to specify
access floor systems; however,
the test is not representative
of an actual installation
because it is performed with
the panel resting on blocks,
not understructure.
System
Performance Criteria (Tested
on Actual Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
All
Steel 1000
Bolted
Stringer
6.0
1000
PASS
350
400
400
150
1000
All
Steel 1250
Bolted
Stringer
7.0
1250
PASS
400
500
500
150
1250
All
Steel 1500
Bolted
Stringer
8.5
1500
PASS
450
600
600
150
1500
System
Performance Criteria (Tested
on Actual Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
Concore
1000
Posilock
7.5
1000
PASS
350
800
600
150
1000
Concore
1250
Posilock
8.5
1250
PASS
400
1000
800
150
1250
System
Performance Criteria (Tested
on Actual Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
Concore
1000
Bolted
Stringer
9.0
1000
PASS
350
800
600
150
1000
Concore
1250
Bolted
Stringer
10.0
1250
PASS
400
1000
800
150
1250
Concore
1500
Bolted
Stringer
10.5
1500
PASS
450
1250
1000
150
1500
Concore
2000
Bolted
Stringer
11.5
2000
PASS
550
1500
1250
150
2000
Concore
2500
Bolted
Stringer
12.0
2500
PASS
650
1500
2000
150
2500
*A
full definition of Design Loads and
Safety Factors can be found in the
Technical Bulletin section of our
website.
All
other tests are conducted under CISCA's
recommended test procedures for access
flooors.