System Performance Criteria
The Performance Charts below are divided into two sections to help you evaluate the overall performance of the systems.  The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.  Panel Only Criteria such as Concentrated Load is often used to specify access floor systems; however, the test is not representative of an actual installation because it is performed with the panel resting on blocks, not understructure. 
System Performance Criteria (Tested on Actual Understructure)
Panel Criteria
(For reference only)
Panel
Understructure SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED LOADS @
<
0.100"
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
All Steel 1000
Bolted Stringer

6.0

1000
PASS
350 
400
400
150
1000
All Steel 1250
Bolted Stringer

7.0

1250
PASS
400 
500
500
150
1250
All Steel 1500
Bolted Stringer
8.5
1500
PASS
450
600
600
150
1500


System Performance Criteria (Tested on Actual Understructure)
Panel Criteria
(For reference only)
Panel
Understructure SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
CONCENTRATED LOADS @
<
0.100"
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
Concore 1000
Posilock

7.5

1000
PASS
350 
800
600
150
1000
Concore 1250
Posilock

8.5

1250
PASS
400 
1000
800
150
1250


System Performance Criteria (Tested on Actual Understructure)
Panel Criteria
(For reference only)
Panel
Understructure SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
CONCENTRATED LOADS @
<
0.100"
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
Concore 1000
Bolted Stringer

9.0

1000
PASS
350 
800
600
150
1000
Concore 1250
Bolted Stringer

10.0

1250
PASS
400 
1000
800
150
1250
Concore 1500
Bolted Stringer
10.5
1500
PASS
450
1250
1000
150
1500
Concore 2000 Bolted Stringer
11.5
2000
PASS
550
1500
1250
150
2000
Concore 2500 Bolted Stringer
12.0
2500
PASS
650
1500
2000
150
2500

*A full definition of Design Loads and Safety Factors can be found in the Technical Bulletin section of our website.  All other tests are conducted under CISCA's recommended test procedures for access flooors.